Carrier furnace stops heating after 30 minutes (LED status code 33)

(adsbygoogle = window.adsbygoogle || []).push({ google_ad_client: "ca-pub-4807877879849697", enable_page_level_ads: true });

Carrier furnace (59SC5A series) stops heating about 30 minutes after start up. The blinking LED shows a pattern of 3 short flashes and 3 long flashes, i.e. status code 33.

From the Troubleshooting Guide,

33 LIMIT CIRCUIT FAULT – Indicates the limit, flame rollout is open. ……. Flame rollout switch requires manual reset. Check for:

  1. Loose blower wheel.
  2. Dirty air filter or restricted duct system.
  3. Improper gas input adjustment.
  4. Defective switch or connections.
  5. Improper limit switch or no gasket unless noted on switch.

If open is longer than 3 min, code changes to 13 LIMIT CIRCUIT LOCKOUT. ”

So, what does it mean?

It means (A) overheating in the heat exchange, (B) defective switch or connections, (C) improper limit switch, or (D) fire outside the heat exchange.

Troubleshooting steps:

(A) Overheating:

Higher than expected temperature in the heat exchange.

  • 1. Loose blower wheel (i.e. not providing sufficient air circulating through the heat exchange)
    fix or replace the blower wheel.
  • 2. Dirty filter or resisted duct system (i.e. not providing sufficient air circulating through the heat exchange)
    replace a clogged furnace filter, unblock all cold-air return vents and floor/ceiling registers, and/or increase blower speed.
  • 3. Improper gas input adjustment (i.e. improper gas input to furnace burners)
    adjust gas input by a gas technician or furnace contractor.

(B) Defective switch or connections:

  • 4. Defective switch or connections (i.e. limit switch and flame rollout switches)
    check wire connections to limit switch and flame rollout switches.
    – check the limit switch and flame rollout switches are not open in a normal condition, i.e. resistance value of the limit switch and flame rollout switches should not be very high.
    – check the temperature inside the heat exchange when the limit switch is open by a gas technician or furnace contractor.

(C) Improper limit switch:

  • 5. Improper limit switch (i.e. the limit switch opens at the temperature below the heat exchange operating temperature )
    – check both the limit switch cutoff temperature (on the label) and the furnace specification. For example, if the furnace specification requires a limit switch of cutoff temperature at 170 degree F and the existing limit switch cutoff temperature is 140 degree F, the furnace will shut off at 140 degree F instead of the specified cutoff temperature of 170 degree F.

(D) Fire outside the heat exchange:

  • Fire is detected outside the heat exchange by the flame rollout switch (i.e. burners are designed to fire in the heat exchange cells only)
    contact a gas technician or furnace contractor for further investigations.
    – possible causes: negative pressure in the furnace room, burner damage, … etc.

 

Reference: Installation, Start-up, Operating and Service and Maintenance Instructions, 59SC5A Single Stage 4-Way Multipoise Condensing Gas Furnace Series 1 and 2.

[amazon asin=&template=banner easy]